Continuous recording and stochastic analysis of PD

1995 
We describe the design and use of a digital partial discharge (PD) data recording system capable of continuous real-time recording of PD pulse trains. The recording system consists of a custom two-channel PD digitizer coupled to a personal computer via a 10-bit parallel interface. The digitizer is under software control with the resulting data being stored in binary files on the computer's hard disk. The stored data subsequently are subjected to stochastic analysis using appropriate computer software. Because all data are retained and the computer provides the desired stochastic analysis of data files, the new system is well suited to investigate non-stationary PD behavior such as encountered in aging studies. By way of illustration, the new system was used to determine the time-varying stochastic behavior of ac-generated PD from point-to-dielectric gaps in air where the insulation material was cast epoxy with aluminum oxide filler. The results confirm and extend previous measurements made with an analog stochastic analyser. With these sample results, we demonstrate how the system allows detailed stochastic analyses not possible with data obtained from existing conventional PD measurement systems. >