Refrigeration assisted spot cooling of a high heat density data center

2004 
Analytical modeling of two kinds of direct expansion refrigeration cooling evaporator and a secondary liquid cooling fan coil heat exchanger is incorporated with computational fluid dynamics (CFD) model to analyze a high heat density electronic and computer data center installed on a raised floor. Both models incorporate an accurate tube-by-tube thermal hydraulic modeling of the heat exchanger. The refrigeration coil analysis incorporates a multi region heat exchanger analysis for a more precise modeling of two phase refrigerant flow in the evaporator. The single phase secondary loop fan coil heat exchanger modeling uses an effectiveness method for regional modeling of the spot-cooling coil. Using an iterative method, results of the heat exchanger modeling is simultaneously incorporated in the CFD model and an optimal design of spot cooling heat exchanger is developed.