Reduced-order model to estimate safe flammable refrigerant charge limits for a one-room air conditioner.

2019 
The Heating, Ventilation, Air-Conditioning and Refrigeration (HVACR revision of the codes is needed to facilitate wider use of flammable alternatives. Hence, information is needed to enable reliable estimates of safe charge limits for flammable refrigerant options for different HVAC&R applications. A reduced-order model (ROM) was developed and validated to help estimate safe charge limits based on computational fluid dynamics (CFD) simulations of refrigerant releases in a single room for a range of parameters. Validation of the ROM vs. the CFD results showed good general agreement for mean refrigerant concentration. The normalized mean bias error (NMBE) was 0.67% with a maximum error of 15%.
    • Correction
    • Source
    • Cite
    • Save
    • Machine Reading By IdeaReader
    0
    References
    0
    Citations
    NaN
    KQI
    []