Analysis of ELF Magnetic Field Reduction Ratio on Passive Loop Using Scale Down Model of Transmission Line

2006 
In this research magnetic field reduction effect of each passive loop was analyzed by using the scale down models of transmission lines. This paper examined magnetic field reduction effect of the passive loop that will be applied to actual facility through the experiment, which is about double vertical transmission line and horizontal transmission line. Consequently, by confirming the fact that magnetic field reduction effect can be obtained to 50 % by passive loop without reactive compensation, we insured technology about application of passive loop. And the case of 3 turns of loop showed two times reduction effect than that of 1 turns of loop in reducing magnetic field. Vertical passive loop is more efficient than horizontal passive loop in the aspect of reducing magnetic field on double vertical transmission lines. What is more, vertical passive loop showed good effect of reducing magnetic field in a far distance as well as in a short distance.
    • Correction
    • Source
    • Cite
    • Save
    • Machine Reading By IdeaReader
    0
    References
    0
    Citations
    NaN