Novel Auto-Reclosing Blocking Method for Combined Overhead-Cable Lines in Power Networks

2016 
This paper presents a novel auto-reclosing blocking method for combined overhead-cable lines in power distribution networks that are solidly or impedance grounded, with distribution transformers in a delta connection in their high-voltage sides. The main contribution of this new technique is that it can detect whether a ground fault has been produced at the overhead line side or at the cable line side, thus improving the performance of the auto-reclosing functionality. This localization technique is based on the measurements and analysis of the argument differences between the load currents in the active conductors of the cable and the currents in the shields at the cable end where the transformers in delta connection are installed, including a wavelet analysis. This technique has been verified through computer simulations and experimental laboratory tests.
    • Correction
    • Source
    • Cite
    • Save
    • Machine Reading By IdeaReader
    10
    References
    4
    Citations
    NaN
    KQI
    []