Removal of H{sub 2}S, methyl macapton dimethyl sulfide and dimethyl disulfide with biofiltration

1996 
A pilot study describes the biofiltration process control that was necessary to remove H{sub 2}S, methyl mercaptan, dimethyl sulfide, and dimethyl disulfide, when mixed in an airstream. A pilot test at a waste water treatment facility was operated over a six month period. During that time H{sub 2}S was removed with very high efficiency at concentrations that reached to 400 ppm{sub v}; H{sub 2}S loading reached as high as 20 gms/m{sup 3}/hr. Methyl mercaptan and the organic sulfides were not removed sufficiently to deodorize the air-stream until a second stage biofilter was added. An odor analysis indicated that the odor detection level was approximately 250,000 odor units at the inlet and 1100 odor units at the outlet. The sulfur distribution in the media indicated that elemental sulfur and sulfate is deposited as a byproduct of the H{sub 2}S oxidation. Data from a fall scale biofilter treating H{sub 2}S from a pumping station is also presented. This data shows very efficient removal of H{sub 2}S, no organic reduced sulfur compounds were found in this air-stream.