Application of a SFCL for Fault Ride-Through Capability Enhancement of DG in a Microgrid System and Relay Protection Coordination

2016 
Concerning that a short-circuit fault happens inside a microgrid system, parts of distributed generation (DG) units may not meet the fault ride-through (FRT) requirements and will be enforced to disconnect. This paper suggests a modified flux-coupling-type superconducting fault current limiter (SFCL) to improve the DG's FRT capability, and investigates the relay protection coordination in the microgrid. The SFCL's structural principle is introduced, and according to the fault characteristic of the microgrid under its grid-connected and islanded statuses, the modified SFCL's application fields are conducted. Furthermore, the directional overcurrent protection and differential protection are proposed for the microgrid's two statuses, respectively. Based on the transient simulations in the MATLAB, the SFCL's positive effects on enhancing the DG's FRT capability can be confirmed, and also it will not affect the relay protection coordination. A comparison of the conventional distance relay protection and the proposed protection scheme is performed, and the latter has a better applicability than the former to match the SFCL. Finally, regarding the impacts of fault type and fault resistance on the FRT operation and the proposed protection, technical discussions are performed preliminarily, and the application value of the SFCL integrated with the proposed protection is clarified further.