코어 위치와 종횡비 및 방위에 따른 건물 에너지 부하 분석
2013
In this Study, effect of core position, area ration and orientation of building on energy load is examined using TRNSYS17. This parameters are major parameters of the conceptual design stage. Reference model is square floor plan(1,444m²), centered core and 29% core area ratio. As the results, without considering the building orientation, the annual heating load of central building with 1:1 area ratio is lowest(59.27 kWh/m²yr). As area ratio is bigger, cooling load is lower and heating load is higher. But if we consider building orientation, orders of heating load and cooling load are changed for area ratio and orientation.