The effects of ventilation and filtration on indoor PM2.5 in office buildings in four countries

2021 
Abstract Fine particulate matter (PM2.5) is an airborne pollutant associated with negative acute and chronic human health outcomes. Although the majority of PM2.5 research has focused on outdoor exposures, people spend the majority of their time indoors, where PM2.5 of outdoor origin can penetrate. In this work, we measured indoor PM2.5 continuously for one year in 37 urban commercial offices with mechanical or mixed-mode ventilation in China, India, the United Kingdom, and the United States. We found that indoor PM2.5 concentrations were generally higher when and where outdoor PM2.5 was elevated. In India and China, mean workday indoor PM2.5 levels exceeded the World Health Organization's 24-hour exposure guideline of 25  μ g/m3 about 17% and 27% of the time, respectively. Our statistical models found evidence that the operation of mechanical ventilation systems could mitigate the intrusion of outdoor PM2.5: during standard work hours, a 10  μ g/m3 increase in outdoor PM2.5 was associated with 19.9% increase in the expected concentration of indoor PM2.5 (p