THE STUDY OF ASPIRATING SMOKE DETECTOR SYSTEM WITH FIRE DYNAMICS SIMULATOR
2015
This study has employed a Fire Dynamics Simulator that is based on Fluid Dynamics to simulate the application of Aspirating Smoke Detector System in High-ceiling Spaces. The FDS simulation result has been analyzed and compared with Full-Scale Smoke Experiments. According to the study results, the alarm would be set off about 10-30 seconds sooner when applying FDS simulation. However, the result of FDS simulation might be too optimistic to have a secure fire protection planning. Therefore, a safety limit should be set for ASD Design with FDS Simulation for a closer result to the actual smoke experiment. However, the ratio of the safety limit will still need to be derived from more experimental analysis and statistics.