Correlation of various RI meters and reading comparison of RI meter operators on a 735 kV line

1967 
The results of a study sponsored by Working Group No. 1 of the RI Subcommittee on Hydro Quebecs 735 kV line are described. Various RI measuring techniques were used in obtaining frequency spectrum and lateral profiles. Radio noise measuring locations were studied and compared with measuring practices for determining statistical RI levels of operating ehv lines. Comparison between different RI meters has indicated that in the broadcast band the Stoddart NM20B reads 1 to 3 db higher than the Siemens. An RI measuring test among 14 master operators indicated the human error to be plus or minus 2 db.
    • Correction
    • Source
    • Cite