Experimental Study on Particle Distribution under Stratified Air-conditioning in Large Space Building

2020 
Particle concentration distribution rule in large space building under HVAC system is very important, because that is related to particle removal solution design. This paper mapped particle concentration distribution in a large space factory under stratified air condition system. The results shows that: large particle concentration shows significant variation along vertical direction, with a max difference of 8 times; the highest particle concentration appears at the height of 1.5 m of all particle sizes; relatively low particle concentration appears between 3 and 6 m; and, a relatively high value appears between 7 and 9 m, which seems to tell there is a stagnation zone of large particles at this height. Nozzle side supply air shows better particle spatial remove efficiency than columnar down supply air.