Simulation of reverse power relay in 11 kV generator protection

2021 
This paper proposed the modelling and simulation of generator protection for power system using digital reverse power relay. The operations of the power plant are often interrupted by the reverse power generation. Therefore, generators need to be closely monitored and controlled. In this study, 11 kV synchronous generators are connected to 220 kV load through a step-up transformer, and a new model of reverse power relay is added for generator protection. The reverse power relay proposed in this paper is a digital relay with high accuracy and high reacting speed. Several cases based on various types of mechanical inputs to the generator were studied to test the operation of the reverse power relay. This simulation was done using MATLAB/Simulink. The results show that the 11 kV generator protection is successful with this new model reverse power relay. Besides, the simulation results were similar result compared to the theory result. From the simulation results, the integral output of the relay will reach the threshold value ‘L’ whenever there is a reversed power flow fault found in the system. Consequently, the relay will be triggered to provide protection for the generator. This model has been added into online resources of MATLAB Power System Tools. In addition, this model may also help the engineers to develop the analytical skills under various conditions.
    • Correction
    • Source
    • Cite
    • Save
    • Machine Reading By IdeaReader
    9
    References
    0
    Citations
    NaN
    KQI
    []