Internal insulation failure mechanisms of HV equipment under service conditions

2005 
Failure mechanisms in oil-barrier transformer insulation and oil-paper condenser type insulation of transformers and HV bushing were discussed with reference to typical defects and failure modes of oil-barrier insulation of transformers, shunt reactor, condenser type bushing and instrument current transformers. It was noted that insulation problems predominantly involve the impairment of insulation, and that the relative rate of major failures in shunt reactors is about 1 per cent. It was suggested that bushings can cause about 45 per cent of major transformer failures, with aged mode failure occurring most frequently. The failure rate of 220-500 kV CTs accounts for more than 60 per cent of total instrument transformer failures. Two failure modes were observed: ionisation-mode and aging-mode failures. The reduction of switching surge breakdown voltage due to deposit of insoluble aging products was discussed. A long-term dielectric strength test revealed the following 2 mechanisms of insulation breakdown: accidental breakdown during the first period of aging and wearing mode breakdown due to degradation of materials at the last stage of the calculated terms of aging. Issues concerning the mechanism of the incipient irreversible failure in oil-barrier insulation were discussed, as well as issues concerning creeping discharge and large failures during normal operating conditions. It was suggested that the occurrence of surface discharge is associated with increased voltage due to oil breakdown progressing into insulation destruction and surface discharge as a self-firing phenomenon. Failure modes induced by peculiar oil and staining of internal porcelain were reviewed. It was noted that the discharges across the inner part of the transformer and porcelain were the out-come of a typical aging-mode phenomenon in the bushing. In addition, failure modes induced by staining the outer surface of bottom porcelain were discussed, as well as failure of oil-filled paper insulation of non-sealed bushings of HV circuit breakers. Details of an investigation of insulation specimens were also presented. The supposition that moistening of oil in non-sealed equipment followed by X-wax tonnation can be the cause of PD occurrence in paper-oil insulation in uniform field was confirmed. 2 refs., 3 tabs.
    • Correction
    • Source
    • Cite
    • Save
    • Machine Reading By IdeaReader
    0
    References
    40
    Citations
    NaN
    KQI
    []