Post-occupancy Evaluation for Energy Conservation, Superior IEQ & Increased Occupant Satisfaction

2013 
This paper proposes a method comprising procedures to calibrate an EnergyPlus whole building energy model. An occupant behavior data mining procedure is developed and tested in an office building. Workday occupancy schedules are generated by mining the office appliance energy consumption data. Hourly and monthly power, energy, and temperature data are collected and used for lighting, equipment and HVAC systems energy performance calibration. The result shows a 1.27% mean bias error for the total annual energy use intensity. The proposed calibration method provides a scientific and systematic framework to conduct high accuracy EnergyPlus model calibration.