Simulation Study on Amplitude of the Overhead Line Based on Simulink

2013 
Aeolian vibration often occurs in the high-voltage transmission overhead lines, and the amplitude of conductors has close relationship with conductors fretting wear. It is very difficult to measure actual amplitude of working conductor, so obtaining the amplitude of the conductor by the means of simulation is of practical significant to research quantitatively the relationship of the amplitude and the fretting wear. In this paper an imitation test-bed was built. The maximum amplitudes in the different location of a conductor in a test condition were obtained by Simulink software simulating, and the results were compared with the maximum amplitudes obtained by experimental test. The result of this comparison showed that between of them were of good similarity, and the locations of vibration nodes and maximum amplitudes were basically same. It was proved to be feasible that the aeolian vibration amplitude of the overhead conductor in kinds of conditions could be obtained by Simulink software simulating.