Investigation on Partial Discharge Activity inside the Cable Accessories due to Improper Installation of Power Cable Joints
2019
This paper presents investigation on partial discharges (PD) activity inside the components of cable accessories. Due to the improper installing (poor workmanship) of cable joints, various types of defects could appear. The epilogue of such condition is the resulting risk for the long or even short term behavior of the insulation system, which exactly depends on the type, form, size and location of the defect. Defect site mostly results in field enhancement and generates partial discharge activities. Investigation is done through the simulation evidences using contemporary software tool COMSOL Mph. to perceive the field enhancement due to the presence of defects. Also, laboratory testing for two artificially induced defects, in order to validate the simulations from the aspect of PD occurrence at defect site, are provided in this paper.