착색단고추 재배용 1-2W형 개조온실 구조의 안정성 검토

2008 
This study was performed to check the structural safety of modified 1-2W Greenhouses to be utilized for growing Paprika. This type of greenhouse was derived from being remodeled by enhancing the column height of conventional 1-2W type greenhouses. According to the results of structural analysis performed by SAP-2000, there was not significant change in critical snow depth in spite of increasing the column height of 1.2 m by welding. But the critical wind velocities were shown to be 26.0~41.0 ㎧, which were 3~18% lower wind velocities compared with those critical velocities estimated for typical type of 1-2W greenhouse. Under the wind loads, those maximum section forces such as shear force, axial force, and bending moment, together with the deformed frame shape of strained greenhouse, were almost similar in both typical type and modified type. Maximum bending moment of column was found at eave's height of column on windward side. Under the snow loads, those maximum section forces such as shear force, axial force, and bending moment, together with the deformed frame shape of strained greenhouse, were almost similar in both typical type and modified type. Maximum section forces except axial force was found at eave's height of column. Maximum axial force was found at inner column. Soil bearing capacity together with the total foundation resistance against wind upheaval was found to be consistently safe enough to resist to both wind load and snow load.