Electrical breakdown voltage of transformer oil with gas bubbles

2014 
Electrical breakdown strength of liquid-gas micro bubble mixtures of transformer oil with sulfur hexafluoride and air for the case of quasi homogeneous gas inclusions distribution and 10% volumetric gas content was experimentally investigated. DC voltage up to 140 kV was applied to a 8 mm gap between hemispherical electrodes. It is shown that transformer oil bubbled with air leads to threshold breakdown voltage decrease by 34% and 19% when bubbled with sulfur hexafluoride. The stabilization effect of sulfur hexafluoride micro bubbles on the value of threshold breakdown voltage is observed.
    • Correction
    • Source
    • Cite
    • Save
    • Machine Reading By IdeaReader
    7
    References
    22
    Citations
    NaN
    KQI
    []