Wind-driven natural ventilation in a low-rise building: A Boundary Layer Wind Tunnel study

2013 
Abstract Indoor Air Quality (IAQ), energy efficiency through passive building design strategies and sustainable construction practices have been highly prioritized in recent years. This paper presents a Boundary Layer Wind Tunnel study on wind-driven natural ventilation for a low-rise building at a model-testing scale of 1:20. The experiment consists of testing various size openings in a single wall, opposite side walls and adjacent side walls with and without portioning walls, with and without opening cover screens, with and without internal volume correction for 36 different wind angles of attacks (unless symmetrical). For the size of the building and openings considered, the experimental analyses indicated that internal volume correction using velocity scaling was important, although this criterion could be relaxed for cross-ventilation with openings in opposite walls. The internal pressure due to cross-ventilation was 1.5–2.5 times higher for A inlet / A outlet  > 1 compared with ratios A inlet / A outlet C d_total and the ventilation rate Q /( V r A ) increased with an increase of the opening ratio. The inlet discharge coefficients obtained in this experiment ranged from 0.65 to 1.08, similar to the results of various early studies.
    • Correction
    • Source
    • Cite
    • Save
    • Machine Reading By IdeaReader
    27
    References
    26
    Citations
    NaN
    KQI
    []