Validation of long term performance of natural ester and Kraft paper as high temperature insulation system

2017 
In early 2003, CPFL Energia, a Brazilian utility, was interested on evaluating the performance of natural ester filled transformers, especially regarding the highly increased overloading capability. As a field test, in association with the transformer manufacturer “Itaipu Transformadores”, they built two prototype transformers. Based on original overhead distribution line three phases transformers of 15kV/45kVA, after small adjustments in the windings and cooling system, keeping same core and tank, associated with the use of natural ester based dielectric liquid, and increasing the average winding temperature rise limit from 55°C to 85°C and a hotspot temperature rise limit of 100°C, the transformer nominal rating was shifted to 88kVA.