Application of Iterative Feedback Tuning Method in Superheated Steam Temperature Control System
2021
Taking a 600 MW supercritical once-through boiler as the study object, this paper designed an IFT-based two-degree-of-freedom (DOF) PID superheated steam temperature control system. Besides, the IFT-PID controller was formed and compared with the conventional tuning method. The simulation results show that this method can be successfully applied to great-inertia and large-lag controlled objects, with evident superiority.