Experimental Demonstration of Frequency Regulation by Commercial Buildings—Part I: Modeling and Hierarchical Control Design

2018 
This paper is the first part of a two-part series in which we present results from one of the first worldwide experimental demonstrations of frequency regulation in a commercial building test facility. We demonstrate that commercial buildings can track a frequency regulation signal with high accuracy and minimal occupant discomfort in a realistic environment. In addition, we show that buildings can determine the reserve capacity and baseline power a priori , and identify the optimal tradeoff between frequency regulation and energy efficiency. In part I, we introduce the test facility and develop relevant building models. Furthermore, we design a hierarchical controller for the heating, ventilation, and air conditioning system that consists of three levels: 1) a reserve scheduler; 2) a building climate controller; and 3) a fan speed controller for frequency regulation. We formulate the reserve scheduler as a robust optimization problem and introduce several approximations to reduce its complexity. The building climate controller is comprised of a robust model predictive controller and a Kalman filter. The frequency regulation controller consists of a feedback and a feedforward loop, provides fast responses, and is stable. Part I presents building model identification and controller tuning results. Specifically, we find out that with an appropriate formulation of the model identification problem, a two-state model is accurate enough for use in a reserve scheduler that runs day-ahead. In part II, we report results from the operation of the hierarchical controller under frequency regulation.
    • Correction
    • Source
    • Cite
    • Save
    • Machine Reading By IdeaReader
    34
    References
    56
    Citations
    NaN
    KQI
    []