Predictive pre-cooling of thermo-active building systems with low-lift chillers

2011 
This article describes the development and experimental validation of a data-driven model predictive control algorithm that optimizes the operation of a low-lift chiller, a variable-capacity chiller run at low pressure ratios, serving a single zone with a thermo-active building system. The predictive control algorithm incorporates new elements lacking in previous chiller pre-cooling control optimization methods, including a model of temperature and load-dependent chiller performance extending to low-pressure and part-load ratios and a data-driven zone temperature response model that accounts for the transient thermal response of a concrete-core radiant floor thermo-active building system. Data-driven models of zone and concrete-core thermal response are identified from monitored zone temperature and thermal load data and combined with an empirical model of a low-lift chiller to implement model predictive control. The energy consumption of the cooling system, including the chiller compressor, condenser fan...
    • Correction
    • Source
    • Cite
    • Save
    • Machine Reading By IdeaReader
    41
    References
    31
    Citations
    NaN
    KQI
    []