Theoretical Analysis of Effects of Solution Heat Exchanger on the Performance of Mixed Absorption Refrigeration Cycle

2012 
The model of solution heat exchangers of mixed absorption refrigeration cycle was developed. The effects of strong solution temperature difference between inlet and outlet of solution heat exchanger on the coefficient of performance (COP) and cooling water flow rate of mixed absorption refrigeration cycle were analyzed, at the same time, the effects of temperature difference on the unit heat exchange area of counter-flow and cross-flow solution heat exchangers were analyzed. The theoretical analysis results showed that there was an optimal value for the strong solution temperature difference, for the mixed absorption system, the optimal temperature difference was about 12°C, the corresponding COP was 11.2% higher and the cooling water flow rate was 7.8% less than that of system without heat exchanger.