Experimental Study on Heating Performance of Heat Pump Chiller under Overload, Frost and Defrost Conditions
2011
ABSTRACT:In the present study, the performance characteristics of the heat pump chiller under heating conditions were experimentally investigated. Capacity, input power and COP under overload, frost and defrost conditions were obtained. The experimental data for the heat pump chiller were measured using the air-enthalpy calorimeter and the constant temperature water bath. At overload condition, the heating capacity and COP increase about 25.7% and 19.1%, respectively. The variations of the evaporator, the compressor outlet and the condenser temperature were ob-tained under frost and defrost conditions. The frost and defrost period of the heat exchanger decreases about 36.0~56.1%.Keywords:Chiller(칠러), COP(성능계수), Defrost(제상), Frost(착상), Heat pump(히트펌프), Overload(과부하) †Corresponding author Tel.: +82-41-530-2396; fax: +82-41-530-2986 E-mail address: yckweon1@sunmoon.ac.kr 1. 서 론 공조 수요의 확대와 함께 고효율과 고성능화를 추구하는 공조기기 시장에서 히트펌프는 효율성 높은 공조기로 주목받고 있다. (1-3) 또한 공기 열원을 사용하여 기름 및 가스 등을 직접 연소하지 않아 이산화탄소 배출량을 감축하여 친환경적이다. 그러나 외기 온도가 저온으로 갈수록 효율이 급격히 감소하고 실외 열교환기에 발생하는 서리로 효율감소와 서리를 제거하기 위한 에너지소비 증가는 해결해야할 문제로 지적되고 있다.