Evaluation of the Appropriateness of Smoke Control Conditions of Platform at the Subway Fire by using FDS

2013 
In the subway, various fires continue to take place across the world. In the Daegu subway accident in 2003, many people were damaged by shortened visibility range caused by toxic gas and smoke. This paper, assuming that a subway fire happens in the Mandeok Station of the subway system in Busan, analyzed different smoke-spreading situations depending on the ventilation situation at its platform (opening of the train doors, operation of ventilation facilities in the tunnel, and working of fire door), using FDS. The calculation proved that it would be more effective to secure evacuation route when the ventilation facilities of the tunnel are not operated, than when they are on. And, it was also found that the case where the doors of the platform to the escape route and only the platform-facing doors of the subway car on fire office are open would be more effective to ventilation than the case where all the doors are open. And, it was found to be important that the fire doors of the platform are working properly.