Methods to reduce bacterial contamination of recycling cooling systems of a CHPP

2015 
Bacterial contamination of circulating and make-up water of the nonconjugated recycling cooling system with evaporative cooling towers of thermal power plants is studied. The nonconjugated recycling cooling system of Naberezhnochelninskaya CHP Plant was selected as the object of study. It was found that circulating water of recycling cooling is highly contaminated with aerobic heterotrophic bacteria. At the same time, make-up water for the cooling system from the Kama River is moderately polluted with anaerobic bacteria. Measurements of biological contamination in different parts of the recycling cooling system showed that populations of colonies of microorganisms abruptly decreases in turbine condensers, which is probably indicative of their death and deposition on the heat transfer surface of the condenser. Calculation using a special program showed that biological contamination of the recycling cooling system poses the greatest risks for clogging of the equipment (seven points on a nine-point scale), its corrosion (two points), and damage to the health of personnel (two points). Rapid development of aerobic bacteria apparently occurs under elevated temperature and intense aeration of water in the cooling tower. It is suggested to periodically monitor the recycling cooling system for biological pollution and to set a timetable for bactericidal treatment of circulating water depending on the level of its bacterial contamination.