Early results of gate valve flow interruption blowdown tests

1990 
Abstract This paper presents the preliminary results of the USNRC/INEL∗∗ high-energy BWR line break flow interruption testing. Two representative nuclear valve assemblies were cycled under design basis vector water cleanup pipe break conditions to provide input for the technical basis for resolving the Nuclear Regulatory Commission's Generic Issue 87. The effects of the blowdown hydraulic loadings on valve operability, especially valve closure stem force, were studied. The blowdown tests showed that, given enough thrust, typical gate valves will close against the high flow resulting from a line break. The tests also showed that proper operator sizing depends on the correct identification of values for the sizing equation. Evidence exists that values used in the past may not be conservative for all valve applications. The tests showed that improper operator lock ring installation following test or maintenance can invalidate in-situ test results and prevent the valve from performing its design function.