Investigation of load current feed-forward control strategy for wind power grid connected inverter through VSC-HVDC

2018 
The VSC-HVDC connection system will be the effective transmission method for the large scale and long distance integrated wind farm. Because of the fluctuating power, the DC voltage will be over-voltage or under-voltage in transmission line which will affect the steady operation of the wind power integrating system. In order to mitigate the DC voltage variation of the grid-connected inverter on the grid side and improve the dynamic response of the system, a load current feed-forward control scheme is put forward. Firstly, this paper analyses stability of a system without additional feed-forward control based on double close loop. Secondly, the load current which can indicate the power changes is introduced to counteract the fluctuation of DC voltage in the improvement control scheme. By simulating the results show that the proposed control strategy can improve the dynamic response performance and mitigate the fluctuation of the active power output of the wind farm.
    • Correction
    • Source
    • Cite
    • Save
    • Machine Reading By IdeaReader
    7
    References
    1
    Citations
    NaN
    KQI
    []