국내 태양열발전단지 건설을 위한 법선면 직달일사량 자원조사
2005
Since the direct normal insolation is a main factor for designing any solar thermal power system, it is necessary to evaluate its characteristics all over the country. We have begun collecting direct normal insolation data since December 1990 at 16 different locations and considerable effort has been made for constructing a standard value from measured data at each station. KIER (Korea Institute of Energy Research's new data will be extensively used by solar thermal concentrating system users or designers as well as by research institutes.
From the results, we can conclude that
1) Yearly mean 5.4 kWh/m2/day of the direct normal insolation was evaluated for clear day all over 16 areas in Korea.
2) Clear day's direct normal insolation of spring and summer were 5.53 kWh/m²/day and 5.84 kWh/m²/day, and for fall and winter their values were 5.3 kWh/m²/day and 4.94 kWh/m²/day respectively. So, spring and summer were higher, and fall and winter were lower than the yearly mean value.
- Correction
- Source
- Cite
- Save
- Machine Reading By IdeaReader
0
References
1
Citations
NaN
KQI