Induction motors connected with a three-phase AC system may malfunction due to reverse phase or open phase faults. Conventional overcurrent relays and overheating relays are used to prevent such accidents; however, their drawbacks include a low response speed and false operation. Therefore, in this study, a digital relay for the reverse-open phase was designed and fabricated. This relay can detect the reverse phase and open phase faults and send a trigger signal to the control circuit. The proposed relay was developed based on a microcontroller. The detection times of the reverse phase and open phase were verified as 320ms and 80ms, respectively. Compared with conventional relays that only protect the motor from one type of fault, the proposed relay can detect both, reverse phase and open phase faults. In addition, the fault detection, identification criterion, and trigger signal patterns can be modified by programming according to the requirements of users.