In the lightning impulse test, the 10 kV fusion voltage transformer intelligent component acquisition port often suffers from functional failure or breakdown. In this paper, experimental measurement and inversion calculation were used to study the electromagnetic disturbance level of smart component acquisition port. During the inversion calculation, the applicability of the dual exponential function model, Heidler function model, and impulse function model as the primary source for describing the lightning impulse device were compared and analyzed. The results show that the double exponential model was used as the calculation source of the primary side lightning waveform, and the inversion calculation results were in good agreement with the actual measurement. In addition, the effects of the primary side lightning voltage peak, wave head, and wave tail parameters on the maximum amplitude of the disturbance waveform calculated by inversion are discussed and analyzed. Based on the analysis results, a sufficient inversion calculation parameter was proposed to estimate the disturbance level of the intelligent component acquisition port. Finally, the measured results were compared and discussed with the IEC 61439 assessment level, and it was suggested that the assessment level of fusion equipment should be modified.