Design and Experimental Analysis of 166 kW Medium-Voltage Medium-Frequency Air-Core Transformer for 1:1-DCX Applications

2021 
The galvanic isolation of solid-state transformers (SSTs) is typically realized with a medium-frequency (MF) magnetic-core transformer (MCT). Previous demonstrations indicate that achieving highly power dense and lightweight MCTs imposes several challenges on the design because of stringent requirements related to insulation and cooling. This work investigates the achievable efficiency of an optimized 166kW / 7 kV air-core transformer (ACT), which is a core part of a DC Transformer (DCX), i.e., an unregulated DC-DC SST with a voltage scaling defined by the transformer turns ratio. The ACT features relatively low complexity of the construction, comparably high coupling values, and high efficiency. Modeling, optimization, and construction of the realized ACT are explained and guidelines regarding insulation, cooling, and shielding of the magnetic stray flux are discussed in detail. Furthermore, the prototype is experimentally validated to demonstrate its full functionality. In the investigated DCX, which is based on a series resonant converter (SRC) topology, the realized ACT is found to achieve a full-load efficiency of 99.5% and an unprecedented gravimetric power density of 16.5 kW/kg. With the use of 10 kV SiC MOSFETs, the complete DCX is estimated to reach an efficiency of 99% at 166kW output power.