Study of Shaking Table Test on Seismic Performance of 750 kV Post Insulator

2014 
The applicability of seismic waves for the seismic performance estimation of 750 kV post insulator has been investigated in full-scale shaking table test. the input seismic waves comprise El Centro seismic wave, Landers seismic wave, sine beat wave and artificial standard wave. The testing results indicate that, high dynamic responses of the equipment can be obtained under artificial standard wave condition. In addition, due to comprehensive enveloping ability and gentle spectral curve, artificial standard wave is ideal for the seismic performance evaluation of 750 kV post insulator in the test. An finite element model has been developed and numerical seismic analysis has been performed. Satisfactory match between the simulated and measured results reveals the reliability of the test. The achievements obtained in this paper are helpful in choosing reasonable input wave for shaking table test, and also provide technical support on determining seismic capacity of high voltage electrical equipment.