Estimating the partial discharge inception and extinction voltage in a non-conductive electrical tree

2018 
Electrical tree growth through polymeric insulation is a key degradation process in HV cables. Partial discharges (PDs) are considered to be the energy conversion path for the tree growth. Several methods have been employed to study PDs in electrical tree channels, including the phase resolved PD (PRPD) pattern and pulse sequence analysis (PSA). Our recent work proposed a new method of estimating the PD inception and extinction voltages in non-conductive tree channel based on the PD signals. Here a typical non-conductive tree in polyethylene is considered. Both PRPD and PSA have been employed. It is found that after the PD inception, the PD inception and extinction voltages decrease with the tree growth, and become stable before breakdown. It is also found that the decrease of PD inception and extinction voltages causes an increase in the average number of PDs per cycle, and the shrinking of the dV-dV plot. In turn, the average number of PDs per cycle, and the dV-dV plot can be used to monitor the change of PD inception and extinction voltage during the tree growth.
    • Correction
    • Source
    • Cite
    • Save
    • Machine Reading By IdeaReader
    7
    References
    1
    Citations
    NaN
    KQI
    []