Impact of Tower Arrangement on the Mitigation of the Electric Field Intensity on the High-Voltage Conductors

2019 
In this paper impact of the tower arrangements on the mitigation of the increased values of the electric field intensity at high-voltage transmission line conductors was investigated. Several configurations of high-voltage towers (horizontal, delta, reverse delta, vertical and split-phase configurations) were analyzed. It assumed that the same height of the lowest phase conductors above the ground and the same value of the connected 400 kV voltage. The calculations were carried out for the values of the electric field intensity on the surface of the conductor and its immediate vicinity. A charge simulation method was used to calculate the electric field intensity on the surface of the stranded conductors and their immediate vicinity.