Simple immunoassay for detection of PCBs in transformer oil

2005 
A rapid and inexpensive procedure to detect polychlorinated biphenyls (PCBs) in transformer oil is needed to facilitate identification and removal of PCB contaminated transformers. Here we describe a simple two-step liquid-liquid extraction using acidic dimethyl sulfoxide in conjunction with an immunoassay for detecting PCBs in transformer oil. The process described is faster and simpler than any previous immunoassay while maintaining comparable detection limit and false negative rate. Cross reactivity data, characterizing the immunoassay response to the four Kanechlor technical mixtures of PCBs in oil, are presented. Forty-five used transformer oil samples were analyzed by gas chromatography-high-resolution mass spectrometry and were also evaluated using the immunoassay protocol developed. Results presented show zero false negatives at a 1.4 ppm nominal cutoff for the transformer oils analyzed.
    • Correction
    • Source
    • Cite
    • Save
    • Machine Reading By IdeaReader
    11
    References
    18
    Citations
    NaN
    KQI
    []