Analysis of linear ground electrodes placed in vertical three-layer earth

1996 
The current distribution, line leakage current density, grounding admittance/impedance, surface potential and magnetic field distribution of linear ground electrodes (LGE) in an inhomogeneous earth of vertical three-layer stratification are presented. This is achieved by using quasi-stationary expressions for potential and a system of integral equations of two potentials (SIE-TP).