Current Tolerance Capability Calculation Model of Transmission Lines and its Application in Overload Protection
2019
AbstractTraditional overload protection depends on pre-set values and cannot reflect the current tolerance capability of the line. If the current of a line exceeds the setting value of its overload protection, then it will be subsequently tripped off and cause power flow transferring, which may trigger the cascade tripping of power grid. So it is of significant importance for the overload protection to accurately evaluate the real-time safety status of transmission line and coordinate with power system control to eliminate the overload. In this article, starting from the mechanism analysis of conductor heat transfer, a thermal network model is established by focusing on radial and circumferential heat transfer paths. The temperature rise response of the network node is obtained through nonlinear iteration. The calculation model, which is verified by a test platform, is better than standard models. Then, the current tolerance capability calculation model of the whole line is constructed on the basis of the...
Keywords:
- Correction
- Source
- Cite
- Save
- Machine Reading By IdeaReader
22
References
2
Citations
NaN
KQI