Characteristics of Jiles–Atherton Model Parameters and Their Application to Transformer Inrush Current Simulation

2008 
We describe a time-domain simulation technique for nonlinear hysteretic transformer behavior based on the Jiles-Atherton model but with variable parameters. The normal Jiles-Atherton model assumes its parameters are independent of the applied maximum (peak) magnetic field intensity H max . In this paper, we demonstrate that these parameters vary with H max for a ferromagnetic material commonly found in transformers and we also propose a technique for modelling transformer behavior when H max is rapidly changing. We present examples of inrush current simulation for transformer protection research and compare them with experimental measurements, demonstrating that the proposed algorithm is robust and accurate.
    • Correction
    • Source
    • Cite
    • Save
    • Machine Reading By IdeaReader
    10
    References
    50
    Citations
    NaN
    KQI
    []