Evaluation of Structural Behavior of Reinforced Concrete Exterior Beam-Column Joints with High-Strength Concrete

2014 
This paper reports the test results of reinforced concrete exterior beam-column joints with high-strength concrete. The main parameters of eight specimens were joint failure modes, the compressive strength of concrete, and the head shapes of steel bars. All specimens were designed according to ACI 352R-02 design recommendations. Two types of failure modes were considered; J-failure and BJ-failure. The longitudinal steel bars were anchored by 90 degree standard hooks or headed reinforcement. Experimental results indicated that the current ACI design recommendation limited by the compressive strength of concrete somewhat underestimated the strength of beam-column joints with high-strength concrete. In the specimens showed joint shear failure, the strength of beam-column joints with headed bars was approximately 10 percent higher than that of joints with 90 degree standard hooks.