With the increased penetration of renewable energy, maintaining the system frequency stability is becoming more and more challenging due to the reduced inertia. This paper proposes an improved short-term over-production control strategy based on the virtual inertia provided by wind turbines. In particular, the limitations of the current short-time over-production control of DFIG wind turbines are investigated, including the excessive release of rotor kinetic energy and the secondary frequency drop. Then, an improved three-stage control strategy is proposed, including the frequency adjustment mode, the speed recovery mode and the maximum power tracking control mode. Test results on the 3-machine 9-bus system verify the effectiveness of the proposed control strategy in improving system transient frequency response performance.