Airborne Infection: Theoretical Limits of Protection Achievable by Building Ventilation

1991 
Of 67 office workers 27 (40%) had documented tuberculin skin test conversions after an estimated 4-wk exposure to a coworker with cavitary tuberculosis. Worker complaints for more than 2 yr before the tuberculosis exposure prompted investigations of air quality in the building before and after the tuberculosis exposure. Carbon dioxide concentrations in many parts of the building were found to be above recommended levels, indicating suboptimal ventilation with outdoor air. We applied a mathematical model of airborne transmission to the data to assess the role of building ventilation and other transmission factors. We estimated that ventilation with outside air averaged about 15 feet3/min (cfm) per occupant, the low end of acceptable ventilation, corresponding to CO2 levels of about 1,000 ppm. The model predicted that at 25 cfm per person 18 workers would have been infected (a 33% reduction) and at 35 cfm, a level considered optimal for comfort, that 13 workers would have been infected (an additional 19% re...