Development of Compact 500 kV 8000 a Gas Insulated Transmission Line-Dust Control during Field Jointing and Method for Detecting Conductive Particles

1987 
This paper describes the results of studies made on dust control during field jointing and a method for detecting conductive particles after installation in the development of a compact 500 kV 8000 A gas insulated transmission line (GIL). The study on dust control during field jointing proved that field jointing of the compact GIL can be done like conventional GIL in an easily fabricated vinyl shelter without a clean air flow. Harmful conductive particles can be detected with an Acoustic Emission (AE) sensor. This sensor is effective in improving the reliability of the compact GIL when used with a suitable ac voltage during field test. A 120 m long test line of compact 500 kV 8000 A GIL was constructed and, in a long-term field test, proved to have properties sufficient for practical use.