등식제약조건을 이용한 전철변전소 상태추정

2010 
Through the process of state estimation in the electric railway substation, this paper presents a new method for improving the reliability of the measurements corrupted by gauge error. Unlike the case of commercial power systems, it has been difficult to perform the state estimation by using the usual methods in the electric railway substation. At some of the monitoring points in the substation, most often, it is hard to define the measurement functions by use of the states or as we set up a new states set with the change of system topology, some of the measurement functions become part of the states themselves, which leads to poor results. To resolve the problems in the existing method caused by the relations between the states and the measurement functions at the monitoring points, the proposed method in this paper exploits the equality constraints. They can be derived numerously and concisely from the current and the voltage attributes of the Scott transformer and the buses connecting conditions, etc. We have proofed the effectiveness of the proposed method by the test on a standard sample substation.