Dielectric Behavior of Compact Design Three Phase Coated Gas Insulated Busduct with Metallic Particle Contamination
2008
The use of a gaseous medium with higher dielectric strength like sulphur hexafluoride (SF6) instead of air helps in manifold reduction in the size of the sub-station component. Compact GIS systems are essentially three-phase common systems with more than one functional element in one enclosure. Metallic particles can be either free to move in the GIS or they may be tuck either to an energized electrode or to an insulator surface. If a metallic particle crosses the gap and comes into contact with the inner electrode or if a metallic particle adheres to the inner conductor, the particle will act as a protrusion on the surface of the electrode, and the voltage required for breakdown of the GIS will also cause a significant reduction of the breakdown voltage. One method of conducting particle control and deactivation is by coating the inner surface of the outer enclosure. To determine the particle trajectories in a three-phase common enclosure gas insulated busduct (GIB) an outer enclosure of diameter 500 mm and inner conductors of diameters 64 mm spaced equilaterally are considered. Aluminum, copper and silver particles were considered to be present on enclosure surface. Simulation of particle movement with reduced phase conductor is also carried out with a view to obtain optimum size of conductor for reliable operation by reducing the original diameter of the conductor from 64 mm to 54 mm in steps of 5 mm.