Verification of automatic coagulant dosage control technology based on aluminum concentration at a water purification plant

2015 
An automatic coagulant dosage control technology for water purification plants was developed to deal with rapid changes of feed water quality. Control logic was developed to decide coagulant dosage based on aluminum concentration in the mixing tanks. A coagulant-sedimentation process apparatus was installed in December 2010 in a water purification plant, and the coagulant dosage control test using feed water was started. The developed system was confirmed to be effective for managing settled water turbidity and adequacy of coagulant dosage. For actual changes of feed water quality at the water purification plant over more than one year, the developed system was able to maintain settled water turbidity at less than 1.0 mg-kaolin/L in the period of high feed-water turbidity.
    • Correction
    • Source
    • Cite
    • Save
    • Machine Reading By IdeaReader
    6
    References
    5
    Citations
    NaN
    KQI
    []