Numerical simulation of shower cooling tower based on artificial neural network

2008 
This study was prompted by the need to design towers for applications in which, due to salt deposition on the packing and subsequent blockage, the use of tower packing is not practical. The cooling tower analyzed in this study is void of fill, named shower cooling tower (SCT). However, the present study focuses mostly on experimental investigation of the SCT, and no systematic numerical method is available. In this paper, we first developed a one dimensional model and analyzed the heat and mass transfer processes of the SCT; then we used the concept of artificial neural network (ANN) to propose a computer design tool that can help the designer evaluate the outlet water temperature from a given set of experimentally obtained data. For comparison purposes and accurate evaluation of the predictions, part of the experimental data was used to train the neural network and the remainder to test the model. The results predicted by the ANN model were compared with those of the standard model and the experimental data. The ANN model predicted the outlet water temperature with a MAE (mean absolute error) of 1.31%, whereas the standard one dimensional model showed a MAE of 9.42%.
    • Correction
    • Source
    • Cite
    • Save
    • Machine Reading By IdeaReader
    10
    References
    29
    Citations
    NaN
    KQI
    []