Characterization of Sustained Series dc Arc Duration for Advanced Detection Schemes

2019 
Series arcs in dc power systems can occur if energized wires split, or load connections become relaxed. Compared to their parallel counterparts, series dc arcs decrease load current, making detection more challenging. Series dc arc models, along with accompanying detection methods have been studied in the past. However, few studies link load and source impedance to the timing of series dc arcs. Using a broad set of data taken at different RC loads with a fixed loop impedance, the minimum required time for a sustained series dc arc to occur was defined. Analytic models describing the transient behavior of series dc arcs are used to link the load and line impedance to this necessary timing condition. The findings in this paper can guide the design of future dc power systems, ensuring current detection and protection schemes may operate within the minimum time window.